Hioki 3390 Power Analyzers
Follow us for the latest equipment specials.
New Hioki 3390
Sell Equipment Repairs Add to cart E-mail this page Alert me when this goes on sale
Hioki 3390 Details
Hioki 3390
The POWER ANALYZER 3390 maximizes the advantages of both clamp-on current
sensors, which provide coverage up to and including the frequencies used by
inverters, and pass-through current sensors, which are capable of measurement at
accuracies approaching directly wired instruments. Leveraging our expertise in
clamp sensor engineering, proprietary HIOKI technology has made possible a
current sensor-driven power meter that delivers high accuracy throughout a broad
frequency range, making it well suited for motor evaluation.
Users can select from inexpensive clamp-on current sensors, which are available
in 20A to 500A AC as well as AC/DC types, to high-precision pass-through current
sensors, based on the requirements of their measurement objective.
Features:
- Ideal for use in the development and evaluation of increasingly
efficient inverter motors
- The 3390's new high-speed power analysis engine provides the motor power efficiency and harmonic measurement functionality needed to develop high-efficiency motors such as those used in hybrid automobiles. Moreover, it delivers high-speed simultaneous measurement with a data refresh rate of 50 ms (6 to 10 times faster than previous HIOKI models).
- The newly developed high-speed power analysis engine eliminates the need for a sampling clock, which was required by previous models to measure harmonics at low motor speeds. The 3390 can perform automatic measurement at the fastest refresh rate from 10 rpm to 100,000 rpm (with a 6-pole motor).
- Ideal for use in the development and evaluation of new energy
sources such as solar and wind power
- The 3390 can simultaneously measure power conditioner input DC power and output AC power while analyzing up to 100th-order harmonics and measuring the distortion factor.
- DC and True RMS current plus power integration functionality lets you measure power drawn from and sold to the grid as well as power consumption and regenerative power.
- Ideal for use in inverter maintenance
- Clamp-on current sensors make it easy to simultaneously measure primary- and secondary-side power while analyzing up to 100th-order harmonics and noise (FFT analysis).
- Compact, lightweight design features an integrated handle for easy portability.
Specifications:
- Basic specifications
- asic accuracy: +/-0.05% rdg. +/-0.05% f.s. (50/60 Hz), +/-1.5% rdg. +/-0.5% f.s. (100 kHz)
- Frequency band width: DC, 0.5 Hz to 150 kHz
- Input: Isolated 4-channel input (support for measurement lines from single-phase to 3-phase/4-wire)
- Measurement items: Voltage, current, active/reactive/apparent power, power factor, phase angle, frequency, efficiency, current integration, power integration, voltage peak, current peak, rms, total harmonic factor, phase difference, distortion, imbalance
- Measurement functionality: Noise measurement; rectification method selection; scaling; averaging; efficiency/loss calculation; Δ-Y calculation; simultaneous measurement of true rms, average value, AC component, DC component, and fundamental harmonic component
- Data refresh rate: 50 ms
- Memory: Support for USB memory sticks and CF cards (support for long-term data storage on high-capacity media)
- Communications interfaces: USB, LAN (including remote operation via a web browser using integrated HTTP server function)
- Synchronized measurement: Supported (Data from up to 4 units can be easily captured and saved by a PC using included software.)
- Temperature measurement: Supported when used in combination with radiation thermometer (connected via RS-232C interface)
- Connection check: By vector display (easy, in-advance detection of improper connections during 3-phase measurement)
- Display: Wide 9" display (800 × 480)
- Options
- Current sensors: AC/DC CURRENT SENSOR 9709, UNIVERSAL CLAMP-ON CT 9277/9278/9279, CLAMP-ON SENSOR 9272-10
- Motor analysis function: Measurement of motor power, motor efficiency, encoder pulse reference phase, and electrical angle
- D/A output: 16-channel (Generate analog output for up to 16 user-selected measurement items, or voltage/current waveforms sampled at 500 kS/s.)
- Printer: With double-sided copy support
- Physical Characteristics
- Dimensions and weight: 340(W) × 170(H) × 160(D)mm, 4.5kg (EIA 4U rack-mountable)