Universal power input. Can be plugged into a std. 120vac receptacle or be hard wired to operate on 120/240vac or DC.
Mechanical relays are easily accessible
Max Switching voltage 28Vdc,277Vac
Rated Current 10A @ 277Vac, 15A @125Vac
Push button diagnostic test
Potentiometers for onsite calibration
The SBS-H2 Hydrogen Detector is a complete hydrogen monitoring system with visual and auditable alarms. The alarm system comes complete with the hydrogen sensor and all the necessary accessories to quickly and easily install the system.
Warning: When at least 1% hydrogen in air is present the yellow warning light will come on and the Warning relay contact will close allowing power to peripheral such as a vent fan or other device.
Alarm: When at least 2% hydrogen in air is present the Red warning light will come on and an audible alarm activates. In addition a second alarm relay contact will close which can be used to shut down the system, initiate a building alarm system, or other devices
Storage Battery Systems SBS-H2 datasheet & specifications